Network Platforms - Status Page

Teraco JB1 planned maintenance - 17 May 2025
Scheduled for May 17, 2025 at 6:00 AM – 4:00 PM about 10 hours
  • Planned
    May 17, 2025 at 6:00 AM
    Planned
    May 17, 2025 at 6:00 AM

    Scheduled Date: 17 May 2025

    Scheduled Time: 08H00 to 18H00

    Expected Duration: 10 Hours

    Teraco has planned scheduled Major Electrical Maintenance at the JB1 East Isando Data Centre TEM3 A FEED.

    The details are as follows:

     

    Description

    • Data Centre 4

    • Data Centre 5

     

    SERVICE IMPACT

    • During planned Major Electrical Work at JB1 East the TEM3 MLV A Feed supply will be switched off and isolated.

    • TEM3 MLV B Feed will remain available.  No redundancy as only TEM3 MLV B Feed will be the source of power.

    • Dual-corded devices will not be affected as B feed will be available.  Customer to ensure dual corded device is split over A and B PDU’s.

    • All single-corded devices connected to the A feed will be off. Customers advised to install ATS units or move power connections to the B feed in advance.

    • Only one feed will be worked on at a time ensuring N resilience at all times.

    • No client installations to be undertaken during this period.

    Maintenance roll back plan in place to mitigate any unplanned or unforeseen circumstances.

    If you have any queries please reach out to support@networkplatforms.co.za