Scheduled for May 10, 2025 at 6:00 AM – 4:00 PM about 10 hours
Planned
May 10, 2025 at 6:00 AM
Planned
May 10, 2025 at 6:00 AM
Scheduled Date: 10 May 2025
Scheduled Time: 08H00 to 18H00
Expected Duration: 10 Hours
Teraco has planned scheduled Major Electrical Maintenance at the JB1 East Isando Data Centre TEM2 B FEED
The details are as follows:
Description
Data Centre 2
Data Centre 3
Data Centre 4
SERVICE IMPACT
During planned Major Electrical Work at JB1 East the TEM2 MLV B Feed supply will be switched off and isolated.
TEM2 MLV A Feed will remain available. No redundancy as only TEM2 MLV A Feed will be the source of power.
Dual-corded devices will not be affected as A feed will be available. Customer to ensure dual corded device is split over A and B PDU’s.
All single-corded devices connected to the B feed will be off. Customers advised to install ATS units or move power connections to the A feed in advance.
Only one feed will be worked on at a time ensuring N resilience at all times.
No client installations to be undertaken during this period.
Maintenance roll back plan in place to mitigate any unplanned or unforeseen circumstances.
Network Platforms infrastructure is dual feed from both A and B feeds and will be unaffected during this maintenance window.